产品标准本产品按GB12706《额定电压35kV及以下铜芯、铝芯塑料绝缘电力电缆》和GB12666《电线电缆燃烧实验方法》标准生产,同时还可根据用户需要按******电工委员会推荐的IEC标准、英国BS标准、德国DIN标准、美国ICEA标准及日本JIS标准生产。 The product is manufactured according to the standard of GB12706 and GB12666 or IEC,BS,DIN,ICEA,and JIS upon request.
适用范围本产品适用于工频额定电压0.6/1kV及以下配电线路或工业装置中有耐火要求的固定敷设场所使用。 The product is suitable for use in power distribution lines or fixed installations with rated power-frequency voltage up to and including 0.6/1kV.
使用特性
·工频额定电压U0/U:0.6/1kV。 Rated power-frequency voltage U0/U:0.6/1kV.
·电缆导体的***高允许长期工作温度(PVC/XLPE):70℃/90℃. Max.permissible continuous operating temperature of conductor (PVC/XLPE): 70℃/90℃
·短路时(***长持续时间不超过5s)电缆导体***高允许温度 PVC:导体截面≤300mm2-160℃ 导体截面>300mm2-140℃ XLPE:250℃ Max.short-circuit temperature of the conductor shall not exceed(5s maxiumduration): PVC:cross-section of conductor≤300mm2-160℃ cross-section of conductor>300mm2-140℃ XLPE:250℃
·电缆敷设时环境温度应不低于0℃ The ambient www.zgsljt.com under installation should not below 0℃
·电缆的弯曲半径:多芯电缆不小于电缆外径15倍,单芯电缆不小于电缆外径20倍。 The bending radius of a single-core cable should not less than 20 times of the cable diameter. The bending radius of multicore-cable should not less than 15 times of the cable diameter.
电缆的型号、名称和用途
|
序 号
|
型 号
|
名 称
|
使用范围
|
1
|
VV VLV VY VLY
|
聚氯乙烯绝缘聚氯乙烯/聚乙烯护套电力电缆
|
敷设在室内、隧道及管道中,电缆不能承受机械外力作用
|
VV22 VLV22 VV23 VLV23
|
聚氯乙烯绝缘聚氯乙烯/聚乙烯护套钢带铠装电力电缆
|
敷设在室内、隧道内直埋土壤,电缆能承受机械外力作用。
|
VV32 VLV32 VV33 VLV33 VV42 VLV42 VV43 VLV43
|
聚氯乙烯绝缘聚氯乙烯/聚乙烯护套钢丝铠装电力电缆
|
敷设在高落差地区,电缆能承受机械外力作用及相当的拉力。
|
2
|
YJV YJLV YJY YJLY
|
交联聚乙烯绝缘聚氯乙烯/聚乙烯护套钢带铠装电力电缆
|
敷设在室内、隧道及管道中,电缆不能承受机械外力作用。
|
YJV22 YJLV22 YJV23 YJLV23
|
交联聚乙烯绝缘聚氯乙烯/聚乙烯护套钢带铠装电力电缆
|
敷设在室内、隧道内直埋土壤,电缆能承受机械外力作用。
|
YJV32 YJLV32 YJV33 YJLV33 YJV42 YJLV42 YJV43 YJLV43
|
交联聚乙烯绝缘聚氯乙烯/聚乙烯护套钢丝铠装电力电缆
|
敷设在高落差地区,电缆能承受机械外力作用及相当的拉力。 | | |