优质DYDL-ZR-VV-0.6/1kv电力电缆
|
|
|
|
|
|
发布时间:2011.12.03 新闻来源:计算机屏蔽电缆 浏览次数: |
|
|
载流量计算条件 |
1.环境温度:25°C:2. 土壤热阻系数;P=1.0°C. m/W; 3. 埋地敷设深度:1000mm; 4.导体温度: 导体长期运行温度为70°C; 5.电缆敷设轴间中心距S== 2D |
型号及电压等级 |
DYDL-RZ-VV、 0.6/1kv |
标称截面积mm² |
参考外径/mm |
载流量推荐值/A |
成品参考 考质量/(kg/km) |
空气中敷设 |
埋地敷设 |
铜芯 |
|
铜芯 |
|
|
|
16.2 |
31 |
|
24 |
|
453 |
|
17.5 |
39 |
|
49 |
|
567 |
|
21.0 |
54 |
|
67 |
|
863 |
|
23.8 |
72 |
|
87 |
|
1222 |
|
28.5 |
96 |
|
111 |
|
1862 |
|
31.3 |
118 |
|
134 |
|
2447 |
|
37.0 |
144 |
|
159 |
|
3257 |
|
42.0 |
186 |
|
199 |
|
4509 |
|
49.1 |
227 |
|
235 |
|
6154 |
|
53.6 |
266 |
|
269 |
|
7518 |
|
59.3 |
303 |
|
302 |
|
9216 |
|
66.0 |
352 |
|
343 |
|
11474 |
|
15.7 |
31 |
|
39 |
|
417 |
|
17.3 |
39 |
|
49 |
|
540 |
|
20.4 |
53 |
|
67 |
|
802 |
|
23.3 |
71 |
|
87 |
|
1139 |
|
27.7 |
95 |
|
111 |
|
1732 |
|
30.6 |
116 |
|
133 |
|
2192 |
|
35.7 |
142 |
|
158 |
|
2962 |
|
40.3 |
183 |
|
198 |
|
4035 |
|
47.2 |
224 |
|
233 |
|
5561 |
|
51.7 |
262 |
|
268 |
|
6886 |
|
56.5 |
297 |
|
300 |
|
8224 |
|
63.0 |
346 |
|
341 |
|
10361 |
|
70.9 |
414 |
|
398 |
|
13294 |
|
78.6 |
481 |
|
452 |
|
16461 |
|
15.3 |
30 |
|
38 |
|
397 |
|
17.0 |
39 |
|
48 |
|
522 |
|
19.7 |
53 |
|
66 |
|
750 |
|
22.0 |
71 |
|
87 |
|
1075 |
|
26.8 |
94 |
|
110 |
|
1611 |
|
28.9 |
115 |
|
132 |
|
1956 |
|
34.2 |
141 |
|
157 |
|
2709 |
|
38.8 |
181 |
|
197 |
|
3658 |
|
44.4 |
222 |
|
234 |
|
4950 |
|
49.0 |
259 |
|
266 |
|
6322 |
|
53.7 |
294 |
|
298 |
|
7343 |
|
60.0 |
340 |
|
338 |
|
9333 |
|
67.5 |
407 |
|
395 |
|
11898 |
|
75.1 |
474 |
|
449 |
|
14800 | | |
本文共分 1 页
|
|
|
|
|